THHN/TFFN Building Wire
UL Listed Types TFFN, THHN/THWNInsulation: PVC (Poly Vinyl Chloride) with Secondary Nylon Jacket
Conductor: Bare Copper Voltage Rating: 600 Volts
Temperature: 90oC dry 75oC wet, dry or in oil (NEC Standard)
General purpose building wire. Resistant to oil, gasoline, water, acids, ozone, alkalines, sunlight, and abrasion.
Download our datasheet here
|
Wire Type |
Dimensional Data |
|||
|
RDS Number |
Gauge |
No. of Strands |
Insulation O.D. |
Weight |
|
|
(AWG) |
|
Nominal |
LBS/1000’ |
|
|
|
|
|
(Nominal) |
TFN SOLID CONDUCTOR (TFN, AWM) |
||||
|
TFN-18-SOL-* |
18 |
1 |
.082 |
7 |
|
TFN-16-SOL-* |
16 |
1 |
.093 |
11 |
|
TFFN STRANDED CONDUCTOR (MTW, TFFN, AWM) |
||||
|
TFN-18-STD-* |
18 |
16 |
.090 |
8 |
|
TFN-16-STD-* |
16 |
19 |
.104 |
12 |
THHN SOLID CONDUCTOR (THHN, THWN, AWM) |
||||
|
THHN-14-SOL-* |
14 |
1 |
.106 |
16 |
|
THHN-12-SOL-* |
12 |
1 |
.123 |
24 |
|
THHN-10-SOL-* |
10 |
1 |
.154 |
38 |
THHN STRANDED CONDUCTOR (MTW, THHN, THWN, AWM) |
||||
|
THHN-14-STD-* |
14 |
19 |
.116 |
17 |
|
THHN-12-STD-* |
12 |
19 |
.135 |
25 |
|
THHN-10-STD-* |
10 |
19 |
.169 |
40 |
|
THHN-08-STD-* |
8 |
19 |
.216 |
64 |
|
THHN-06-STD-* |
6 |
19 |
.260 |
96 |
|
THHN-04-STD-* |
4 |
19 |
.331 |
154 |
|
THHN-03-STD-* |
3 |
19 |
..360 |
190 |
|
THHN-02-STD-* |
2 |
19 |
.394 |
235 |
|
THHN-01-STD-* |
1 |
19 |
.450 |
302 |
|
THHN-1-0-STD-* |
1/0 |
19 |
.490 |
375 |
|
THHN-2-0-STD-* |
2/0 |
19 |
.540 |
465 |
|
THHN-2-0-STD-* |
3/0 |
19 |
.590 |
580 |
|
THHN-4-0-STD-* |
4/0 |
19 |
.650 |
720 |
* = Color.
| 0 = Black | 1 = Brown | 2 = Red | 3 = Orange | 4 = Yellow | 5 = Green |
| 6 = Blue | 7 = Violte | 8 = Gray | 9 = White | Pk = Pink | Tn = Tan |
These colors may also be used for stripe combinations. Example: -54 = Green with one Yellow stripe.
Availability of colors decreases with increase in AWG size. Consult our sale staff for details.